A fire
sprinkler system is an innovation that has been saving properties, assets,
households, and lives for over a century. Modern sprinkler systems are more
complex and effective than ever. They are commonly used in hospitals,
warehouses, offices, schools, and more. However, if the water pressure running
through these systems isn’t sufficient, they may become completely useless.
This is where an electric or diesel fire pump can help you eliminate
water pressure issues.
Let’s
discover more about diesel fire pump
packages!
Electric vs. Diesel Fire Pumps
Both
electric and diesel fire pumps deliver the same results, but their engines
operate in different ways and require different protocols for maintenance and
testing. For instance, electric engines are more common, cheaper, and require
less maintenance.
However, if you
don’t have a backup generator, these engines may become useless when the power
goes out. That said, diesel engines don’t get affected by power outages, making
them more reliable for bigger applications. However, these are more expensive
and require more maintenance protocols to keep them in good working condition.
The Complete Functioning of a Diesel
Fire Pump
To
understand how a diesel fire pump works, you need to understand what a fire
pump is made of. A fire pump is made up of the motor, driver, and controller.
It receives water from either a water tank, underground water supply, or a city
reservoir. The pump boosts the water and supplies it through the sprinkler
system and hose standpipes.
The main
types of diesel fire pumps are the horizontal split-case, vertical split-case,
vertical in-line, and vertical turbine. The most common one is the horizontal
split-case, which is also the most economical one for higher flow applications.
They have long lifespans that make them a popular choice. Another popular
option is the vertical split-case, which is similar to horizontal split-case
fire pumps, except they take up less space. This is because of their vertical
design, which protects the pump from potential flooding damage.
Diesel Fire Pump Inspection and
Testing
All fire
pumps require testing and inspection, but diesel fire pumps require extra care
to ensure that all the valves are in the open position. They must be no-flow or
dry tested, and this should be done weekly. Both the weekly visual inspection
and the dry test are performed by professionals. In the case of electric fire
pumps, they generally require dry-testing only once a month. Diesel fire pumps
must undergo comprehensive annual testing, which puts the whole pump through
its paces. During the test, measure the water pressure and then compare the
measurements to the original design specifications. The point is to make sure
it’s operating effectively.
Diesel fire
pumps should be serviced annually in addition to the inspections and tests.
This service includes replacing fuel filters, testing batteries, fluid levels,
etc. Make sure the maintenance is carried out by someone certified, not just by
any regular technician. Use a fire pump sensing line to take care of the
temperature effect.
Installing Diesel Fire Pumps
As with the
decision on what type of diesel fire pump and system to use, the installation
of the pump should be handled by fire safety professionals. There is an array
of considerations as per the National Fire Protection Association (NFPA) that
need to be followed.
Though
weekly inspections can be done by any personnel on-site, annual and monthly inspections
should be performed by qualified personnel, such as factory-trained and certified
personnel.
What Does
a Fire Pump Sensing Line Do?
A sensing
line or impulse line is used to enable the location of pressure transmitters
away from the process being measured. It is used to reduce the temperature
effects on the transmitter’s performance. Generally speaking, each pump has its
own individual controller, and each controller contains its own individual
sensing line. The fire pump controller is connected to the fire protection
system with the help of piping known as a sensing line. It is connected to the
fire protection system between its discharge control valve pump and discharge
check valve.
One end of
the fire pump sensing line installation is connected to the pressure
sensor within the controller and the other end to the fire pump piping between
the discharge check valve and discharge control valve. This actually provides
the controller the ability to sense any water pressure change occurring in the
fire protection system when the fire pump is functioning. This also allows
testing of the pressure settings even when the discharge control valve is off.
Keep in mind
that…
·
The
sensing line should be non-corrosive and its size must be a minimum of ½-inch.
·
Install
two check valves in each sensing line to absorb pressure surges and avoid the
controller pressure switch from getting damaged.
·
Also,
these check valves should be at least five feet apart.
·
No-flow
testing is required weekly for diesel fire pump packages unless there’s
a risk analysis indicating a different frequency is acceptable.
·
The
pump engine should be run at the rated speed for at least 30 minutes to allow
all its components to warm up.
Let Us Take Care of Your Fire Pump
Needs
With more than
14 years in the business, Callaghan Pump is a leader in the fire protection
industry. We supply branded fire pumps that are equipped with a fire pump sensing line and jockey pump. Enjoy the peace of mind that comes with
knowing your fire protection system is compliant 24/7.
Let us know if you need any help!
No comments:
Post a Comment